(4) Loosen the cap nut and insert
the wire from the bottom of the
enclosure.
Then retract the cable for wiring
through the cap nut.
Cable
Cap nut
Connecting the CT/COM/DRM/SYS Terminal
■
Only where necessary, connect wire cables in accordance with the following procedure.
1) Terminal layout and polarities
Make sure that the wires and polarities are correct.
* If the DRED serves the power, do not connect DRM V - and V+.
COM
DRM
2) Cable types and sizes
CT/COM/SYSTEM Cable PVC Flexible Cable 2C 0.75 mm
◎
DRM Cable CAT5e (10BASE - T/100BASE - TX)
◎
3) Stripping of wire
Please strip as conductor's stripped length related as drawing.
10 to11mm
splayed
* If the cable is shielded, protect the stripped end of the sheath with insulating tape, etc.
4) Connecting
While pressing the release button on the terminal, insert the conductor of the wire all the way into the terminal.
Release button
CT
:Current trancefer
CT
COM
:Network Adaptor(RS485)
SYS
:Communication(RS485)
DRM
:Demand response modes
The demand response modes supported by this product.
◎
SYS
twisted
bent
(5) Tighten the cap nut with proper tightening
torque.
[Tightening torque]
・CT/COM/DRM/SYS Cable gland 2.0-3.0N・m
・GRID-INTERACTIV/STAND-ALONE
Cable gland 3.5-4.5N・m
Cap nut
2
d.c.5V
d.c.5V
d.c.5V
d.c.24V
35