7-10. The Power Rate Limit Setting
• The power rate limit is the ramp rate of real power output in response to changes in power and is defined as a
percentage of rated power per minute.
• The percentage change of the output power limit set by the SET rate 1. The decreasing rate of the output power
limit is set to SET rate-1, and the rate of increase of the output power limit is set to the SET rate + 1.
• The percentage change of the input power limit set by the SET rate 2. The decreasing rate of the input power limit
is set to SET rate-2, and the increasing rate of the input power limit is set by the SET rate + 2.
Parameter Item
SET rate+1
-
SET rate
1
SET rate+2
-
SET rate
2
80
Table Power Rate
Parameter Item
Display
Australia/New Zealand
Default Set Point
16.67%
16.67%
16.67%
16.67%
Range
5.00% ∼
100.00%
5.00% ∼
100.00%
5.00% ∼
100.00%
5.00% ∼
100.00%