No4.07 Volt Response Reference Values Setting - Panasonic LJ-SK56A Installation Manual

Lithium-ion storage battery system
Hide thumbs Also See for LJ-SK56A:
Table of Contents

Advertisement

7-11. Volt Response Reference Values Setting
Volt response mode is to respond to voltage changes at the inverter terminals, and is to increase the number of
systems which can be connected at a point on the grid without adversely affecting the voltage within an electrical
installation.
The volt-watt and volt var response modes shall use the volt response reference values.
※Reference Voltage 4 shuld be set to be equal to or greater than Reference Voltage 3.
Parameter Item
Reference
Voltage 1
Reference
Voltage 2
Reference
Voltage 3
Reference
Voltage 4
82
Table Volt Response Reference Values
Parameter Selection
Display
Australia
Default Set
Range
Point
Setting
207.0V
Disabled
216.0V ∼
220.0V
230.0V
235.0V ∼
250.0V
255.0V
244.0V ∼
265.0V
265.0V
New Zealand
Default Set
Range
Point
Setting
207.0V
Disabled
216.0V ∼
220.0V
230.0V
235.0V ∼
244.0V
255.0V
244.0V ∼
255.0V
265.0V

Hide quick links: