A.1.6 Energy
Energy excluding neutral – over T
with refresh every second. T
is the power integration time in energy calculations; the
int
int
beginning and end of this period are user-controlled.
A.1.6.1 DISTRIBUTION SYSTEM WITH NEUTRAL
Consumed DC energy of phase (i+1) with i ∈ [0 ; 2]:
Total consumed DC energy:
Case 1: Energy consumed other than DC (W[i][n] ≥ 0)
Consumed active energy of phase (i+1) with i ∈ [0 ; 2]:
Consumed apparent energy of phase (i+1) with i ∈ [0 ; 2].
Consumed inductive reactive energy of phase (i+1) with i ∈ [0 ; 2]:
Consumed capacitive reactive energy of phase (i+1) with i ∈ [0 ; 2]:
Consumed distortion energy of phase (i+1) with i ∈ [0 ; 2]:
Consumed non-active energy of phase (i+1) with i ∈ [0 ; 2]:
Total consumed active energy:
Wh[0][3] = Wh[0][0] + Wh[0][1] + Wh[0][2]
Total consumed apparent energy:
VAh[0][3] = VAh[0][0] + VAh[0][1] + VAh[0][2]
Total consumed reactive inductive energy:
VARhL[0][3] = VARhL[0][0] + VARhL[0][1] + VARhL[0][2]
Total consumed capacitive reactive energy:
VARhC[0][3] = VARhC[0][0] + VARhC[0][1] + VARhC[0][2]