AEMC PowerPad 8435 User Manual page 103

3-phase power quality analyzer
Hide thumbs Also See for PowerPad 8435:
Table of Contents

Advertisement

Nominal Range
Measurement Range
Probe Output Signal*
Sensor
Safety
*Output is proportional to the amplitude and frequency of the measured current.
NOTE: Currents <10A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal*
Sensor
Safety
*Output is proportional to the amplitude and frequency of the measured current.
NOTE: Currents <10A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping
Diameter
Safety
NOTE: Currents <0.5A will be displayed as zero. Neutral current measures down to 0A.
Power Quality Analyzer PowerPad
Find Quality Products Online at:
3000A
AC
10A to 6500A
AC
140mV
/3000A
at 60Hz
AC
AC
Length = 24" (610mm); Ø = 7.64" (190mm)
Length = 36" (910mm); Ø = 11.46" (290mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
1000A
AC
10A to 3000A
AC
47µV
/1000A
at 60Hz
AC
AC
Length = 10" (250mm); Ø = 2.75" (70mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
10A to 100A
AC
100mV/A: 100mA to 10A peak
10mV/A: 1 to 100A peak
1000mV peak max
0.46" (11.8 mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT III
®
III Model 8435