Figure 7.18: Kick Start parameter displayed
U e
t
Set Initial Voltage
Normal ramp
Ramp with Kick Start
Figure 7.19: The function of Kick Start
66
Chapter 7
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201

7.5.8 Kick Start

This parameter makes it possible to tune the kick start voltage level which is ap-
plied for a short time duration, before a normal start ramp is performed. Kick Start
provides enough torque during start, but still ensuring a soft start.
It can be set on any of the predefined voltage levels. For each voltage level there is
a fixed time duration relation (t), which is increasing with the different kick voltage
levels. This function can be useful for applications with high initial friction or having
a need of extra power in the first part of the start, as jammed pumps or conveyor
belts. See table 7.2 and graph in figure 7.19.
Table 7.2 Kick Start settings
Kick start setting
Note that the Current Limit function is not working during Kick Start.
Display
Operational time
U e
t
Set Initial Voltage
Normal ramp
Ramp with Kick Start
Kick start voltage
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
Default
Setting range
value
OFF
OFF, 30...100 % Level of Kick Start
Operational time
Kick start time
U e (percent)
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
Description
t (s)
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
0.90
0.95
1.00