Binary Signal Input - ABB i-bus KNX Product Manual

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.11.1.4.5.1
Dependent parameter
Value is sent from a change of
This is displayed if the Send temperature value parameter option includes After a change.
Options:
This parameter determines the temperature change that triggers sending the output value.
7.11.1.4.5.2
Dependent parameter
Every
This is displayed if the Send temperature value parameter option includes After a change.
Options:
This additional parameter sets the interval for cyclic sending.
7.11.1.5

Binary signal input

7.11.1.5.1
Dependent parameter
Maximum dead time
The maximum dead time is 200 ms.
The maximum dead time prevents unwanted multiple operations on the input, e.g. due to bouncing of the
contact.
7.11.1.5.1.1
What is maximum dead time?
An edge change at the input is assessed with a maximum dead time (delay) value of 200 ms. This time
may vary from 0 ms to 200 ms.
No further bouncing is possible.
00.0...01.0...10.0 K
00:00:30...18:12:15 hh:mm:ss
Note
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 185