Adding a module to the base of a column

NN43021-310
Standard 06.01
Adding a module to a column
A module can be added to a column in one of three positions. A specific
procedure is provided for each situation.
"Adding a module to the base of a column" on
"Adding a module between two other modules" on
"Adding a module to the top of a column" on
If the column is equipped with earthquake bracing, the column support rods
must be removed and longer rods must be installed after the module is added.
To change the rods, see "Installing earthquake bracing" on
WARNING
A fully loaded module weighs approximately 60 kg
(130 lbs). More than one person is required to move
a module.
DANGER OF ELECTRIC SHOCK
In a DC-powered system, power to the column can
remain on during the following procedures. In an
AC-powered system, however, power to the entire
column must be shut down throughout the
procedures.
If conduit or other cabling runs through modules that are being moved, you
must tag and disconnect the cables, pull them out of the modules, and reroute
them after all of the modules are repositioned. The top cap can remain on the
module to which it is attached.