Safety ground/protective earth and logic return wiring

To ensure electrical system grounding integrity, follow the isolated ground
topology for all Meridian 1 / Succession 1000M Large System equipment
implementations. Isolated ground provides the best method for avoiding the
introduction of ground noise to the system from other external equipment.
When isolated ground topology is not possible, an alternative grounding
method may be used if it provides the required Meridian 1 / Succession Single
Point Ground (SPG) reference. The SPG source must be the AC Equipment
Ground (ACEG) bus located inside the Meridian 1 / Succession service panel.
Service panel grounding facilities must be properly referenced to an
acceptable AC grounding source, which provides a low noise, low impedance
path.
Installations that have elected not to deploy an isolated ground methodology
will be noted during Avaya system audits. Locations experiencing system
operational performance difficulties attributed to ground noise or improper
grounding methods will be required to rectify the issue.
Installing DC power
Large System Installation and Commissioning
Page 113 of 436