Cabling and connecting the grounding leads

NN43021-310
Standard 06.01
Installing DC power
To eliminate potential of system problems and ensure the best grounding
method possible is used, obtain the services of a certified power contractor or
auditor prior to system installation or cutover.
Note: For a more information about approved ground sources and
methods, see Communication Server 1000M and Meridian 1
Large System Planning and Engineering (NN43021-220). You must use
Insulated ground wire for system grounding.
This section covers cabling and connecting the grounding leads for the
Candeo power system. The Candeo's two grounding leads are:
the frame or safety ground leads for the frames
the battery return reference ground lead for the system
CAUTION
Follow local requirements and electrical code
The grounding methods described in this section are
generic. Specific local, provincial, state or federal
electrical codes and grounding requirements, as well as
specific Customer or communication equipment
requirements shall prevail.
CAUTION
Maintain the integrity of the frame or safety ground
The frame or safety ground shall not be confused with the
reference ground lead, nor with the battery return leads.
The frame or safety ground shall be wired in such a way
as not to be carrying any AC or DC current at any time.