Avaya 1000M Installation And Commissioning Manual page 126

Communication server
Hide thumbs Also See for 1000M:
Table of Contents

Advertisement

Page 126 of 436
Figure 45
Cable routing in the rear of the pedestal – NT4N49AA PDU
BLO CB0 CB1
Cable-tie saddle
NN43021-310
Standard 06.01
Installing DC power
With the NT4N49AA PDU, the safety ground/protective earth wires and all
wiring to the terminal block in the PDU must be neatly routed within the
cable-tie saddles and under the cable restraint bar at the base of the pedestal
(see Figure 45 on
page
PDU cover, safety cover, and rear grill.
Conduit is not required with the NT4N49AA PDU. However, 32 mm (1 1/
4 in.) or 20 mm (3/4 in.) conduit can be used if local codes or individual
installations require it. Conduit can be routed down through the column from
overhead racks or up through the floor. Conduit clamps and the hardware to
fasten the conduit are provided in the pedestal. If the NT7D0902 Rear Mount
Conduit Kit is used, conduit can enter from the rear of the column (above the
floor).
J3
J5
J6
BAT
0/1
March 2013
126). This ensures that there is room to install the
NT4N49AA
J4
+
+
BAT
RTN
RTN
2/3
0/1
2/3
LRTN
Cable restraint bar
FLTR / PWR DIST
UNIT ASSY
CB2
CB3
Cable-tie saddle
553-8989