SIMATIC NET
S7-CPs for Industrial Ethernet
Manual Part B3L
CP 343-1 Lean
6GK7 343−1CX10−0XE0
for SIMATIC S7−300 / C7−300
LED displays
Release 03/2007
C79000-G8976-C198-04
as of hardware version 2, as of firmware version V2.0
TP port:
2 x 8−pin RJ−45 socket
(beneath the front panel)
X = Placeholder for hardware
version

Advertisement

loading

Summary of Contents for Siemens CP 343-1

  • Page 1 SIMATIC NET S7-CPs for Industrial Ethernet Manual Part B3L CP 343-1 Lean 6GK7 343−1CX10−0XE0 for SIMATIC S7−300 / C7−300 LED displays Release 03/2007 C79000-G8976-C198-04 as of hardware version 2, as of firmware version V2.0 TP port: 2 x 8−pin RJ−45 socket...
  • Page 2 The CP ships with a factory-set MAC address. To ensure a unique address assignment, we recommend that you use this factory set MAC address when configuring the module! B3L−2 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 3: Table Of Contents

    ..........6.4.1 Interface for Programming on the PROFINET IO Device CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 .
  • Page 4 ..........CP 343-1 Lean for Industrial Ethernet / Manual Part B3L B3L−28...
  • Page 5: Properties / Services

    ISO-on-TCP connections and TCP connections; The addressing mode can be configured for FETCH/WRITE access as the S7 or S5 addressing mode. − LOCK/UNLOCK with FETCH/WRITE services; CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 B3L−5...
  • Page 6 With the aid of Web diagnostics, you can read out the diagnostic data from a station connected over the CP to a PG/PC with an Internet browser. B3L−6 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 7 You will find further information and Internet addresses in the Preface of the General Part of this manual. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Functions of the CP The range of functions of the CP 343−1 Lean (CX00) can be...
  • Page 8: B3L−8

    6ES7 313−5BF03−0AB0 6ES7 313−6CE00−0AB0 6ES7 313−6CE01−0AB0 6ES7 313−6CF03−0AB0 6ES7 313−6BE00−0AB0 6ES7 313−6BE01−0AB0 6ES7 313−6BF03−0AB0 6ES7 314−6AE01−0AB0 6ES7 314−6AE02−0AB0 6ES7 314−6AE03−0AB0 6ES7 314−6AE04−0AB0 6ES7 314−1AF10−0AB0 6ES7 314−1AF11−0AB0 6ES7 314−1AG13−0AB0 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 9 CPU 317−2 DP CPU 317−2 PN/DP CPU 317F−2 DP CPU 317F−2 PN/DP CPU 318−2 CPU 319−3 PN/DP CPU 614 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Order Number 6ES7 314−5AE03−0AB0 6ES7 314−5AE10−0AB0 6ES7 314−6CF00−0AB0 6ES7 314−6CF02−0AB0...
  • Page 10 C7−636 Keys C7−636 Touch B3L−10 Order Number 6ES7 613−1CA01−0AE03 6ES7 613−1CA02−0AE3 6ES7 633−2BF02−0AE03 6ES7 635−2EC01−0AE3 6ES7 635−2EC02−0AE3 6ES7 635−2EB01−0AE03 6ES7 635−2EB02−0AE3 6ES7 636−2EC00−0AE03 6ES7 636−2EC00−0AE3 6ES7 636−2EB00−0AE3 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 11: Installation And Commissioning

    5. The remaining steps in commissioning involve downloading the configuration data. 6. User diagnostics for commissioning and to analyze problems. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Explanation / Meaning Slots 4 to 11 are permitted for the CP in racks 0 to 3 (connected by IM 360/361).
  • Page 12 Use a screwdriver to set the slider. Note An Ethernet cable can also be inserted and removed with the power supply on. B3L−12 Attachment to Industrial Ethernet: 2 x 8-pin RJ-45 jack CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 13 The power unit for supplying the device must comply with NEC Class 2 as described by the National Electrical Code(r) (ANSI/NFPA 70). The power of all connected power units in total must correspond to a limited power source (LPS). CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 B3L−13...
  • Page 14: Displays

    (not relevant for PROFINET IO data) S RUN: RUN mode S STOP: STOP mode S P1 / P2: Link status of Ethernet port 1 / port 2 B3L−14 DC5V RX/TX STOP CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 15 SF(red) BF (red) (green) − − − Legend: (colored) on CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 STOP CP Operating Mode (yellow) Starting up after power “ON” Stopped (STOP) with errors In this state, the CPU or intelligent modules in the rack remain accessible using PG functions.
  • Page 16 Continuous data transfer at the port over Industrial Ethernet (for example PROFINET IO). (colored) flashing CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Meaning “−” any Release 03/2007 C79000-G8976-C198-04...
  • Page 17: Performance Data

    Operator control and monitoring functions (HMI) S7 connections configured at one end LAN interface − data record length per protocol unit sending receiving CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Explanation / Values 12 maximum...
  • Page 18: Characteristics Of The Send/Receive Interface

    <1 ms at <= 240 bytes per AG_SEND block call: <0.8 ms at <= 240 bytes CP 343-1 Lean for Industrial Ethernet / Manual Part B3L per AG_RECV block call: <1 ms at <= 240 bytes per AG_RECV block call: <0.8 ms at <= 240 bytes...
  • Page 19: Characteristic Data For Profinet Io

    Execution time on the CPU 315−2DP (6ES7 315−2EG10−0AB0) Execution time on the CPU 317−2PN/DP (6ES7 317−2EJ10−0AB0) CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Explanation / Values per PNIO_SEND block call: < 1 ms at 240 bytes per PNIO_SEND block call: <...
  • Page 20: Configuring And Programming The Cp As A Profinet Io Device

    B3L−20 Programming Write the user program for the PROFINET IO device SIMATIC S7 and download it to the SIMATIC S7 CPU. See Section 6.4 Commissioning CP 343-1 Lean for Industrial Ethernet / Manual Part B3L C79000-G8976-C198-04 Release 03/2007...
  • Page 21: Principle Of Data Exchange Over Profinet Io

    In the CPU of the device, the IO data areas for input data and output data are transferred as an entire area to or from one of the data areas (DB, bit memory) including any gaps. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 22: Configuration

    1. Take the required CP from the hardware catalog and insert the module in the SIMATIC 300 station. Figure 6-2 Inserting the CP in a SIMATIC Station in HW Config B3L−22 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 23 6. Select the option “Enable PROFINET IO device operation”. Figure 6-3 Setting the Device Name and the PROFINET IO Device Mode 7. Download the configuration data to the SIMATIC 300 station. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 B3L−23...
  • Page 24: Assigning The Profinet Io Device To A Profinet Io Controller

    2. If no PROFINET IO system exists, select the PROFINET IO controller (for example CP 343−1 EX30/GX21, CP 443−1 EX41, CPU 317−2 PN/DP) and insert a PROFINET IO system (menu “Insert” B3L−24 “PROFINET IO System”). " CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 25 (O address). Figure 6-4 SIMATIC Station with PROFINET IO System with the CP as Device with Input (DI) and Output Modules (DO) CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 “CP 343−1 Lean”.
  • Page 26 IP address assigned by the PROFINET IO controller. If it is overwritten, any configured connections (S7, ISO-on-TCP, TCP) will no longer be established. B3L−26 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 27: Programming

    You will find the precise syntax of the FCs and the meaning of the block parameters in the chapter on FCs in the general part of the manual or in the online help for the block library in STEP 7. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 28: Initialization And Configuration

    During initialization, the data of PNIO_SEND (FC11) is not evaluated and the data of PNIO_RECV (FC12) is initialized with default values. FC11 and FC12 transfer valid data only following the subsequent calls. B3L−28 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 29 FC11 and FC12 each have their own watchdog. Depending on the average CPU cycle time, the connection to the PROFINET IO controller is terminated if one of the two blocks is no longer called following the initialization phase. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 30: B3L−30

    Configuration of a PROFINET IO device in HW Config B3L−30 PNIO_SEND Output area: − Length: 7 bytes − available in DB11 − transferred with FC12 PNIO_RECV CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 PNIO_RECV...
  • Page 31 M 70.1 STATUS := MW 72 CHECK_IOCS := M 70.2 SEND P#DB10.DBX0.0 BYTE 20 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Explanation //PNIO_SEND block call //(transfer inputs to IO controller) //Module address from hardware configuration //No.
  • Page 32 //Address for return parameter NDR //Address for return parameter ERROR //Address for return parameter STATUS //Address for return parameter CHECK_IOPS //Received data in DB11 (7 bytes) //Diagnostic information CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 33: Web Diagnostics

    2. Start the Internet browser and enter the following address in the address line of your Internet browser: http:\\<IP address of the CP> Web diagnostics opens with the “Start Page”. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 “Temporary Internet Files” group box "...
  • Page 34: Diagnostics Pages Of The Cp

    Below the title bar of the start page, you can see the CP type (here: CP 343−1 CX10). Above the navigation panel to the left, you can see the module type (here: “SIMATIC S7 CP”). B3L−34 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 35: Start Page

    Module type Name of the module type Status Operating mode Current mode of the CP: Starting RUN (CP in productive mode) Stopping STOP Stopped with error CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Function B3L−35...
  • Page 36: Identification

    The “write data record” function is explained in detail in the general part A of the manual in the description of the FCs for PROFINET IO. B3L−36 Function CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 37: Rack Configuration

    The last column “LED Status” contains more information. Module name Name of the module configured in HW Config Order number Order number of the module CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Function B3L−37...
  • Page 38 The number of type of the LEDs depends on the particular module type. You will find an explanation of the significance of the LEDs in the documentation for the particular module. B3L−38 Function CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 39: Diagnostic Buffer

    Displays the diagnostic buffer entry (entries only in English) Details: “no. of the event” Event ID Event ID of the diagnostic buffer entry Text of the event entry CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Function B3L−39...
  • Page 40: Industrial Ethernet

    Displays the current network properties (transmission rate and direction). Possible values: 10 Mbps half duplex 10 Mbps full duplex 100 Mbps half duplex 100 Mbps full duplex B3L−40 Function CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 41 Number of the port used for the UDP connection Partner port Number of the port on the partner used for the UDP connection CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Function Function Function B3L−41...
  • Page 42: Profinet Io

    PROFINET IO mode of the CP (here: PROFINET IO device): PROFINET IO controller PROFINET IO device No PROFINET IO configuration Device name Device name IP address IP address of the device B3L−42 Function CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 43 (the blocks are not called or not correctly called) Assigned PNIO controller Device name Device name of the assigned controller IP address IP address of the controller CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Function B3L−43...
  • Page 44: Compatibility With Predecessor Products

    For new user programs, please make sure that you always use the latest block versions. You will find information on the latest block version and links to download the current blocks on the Internet: http://www4.ad.siemens.de/WW/news/en/8797900 B3L−44 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 45 When replacing an older module with the module described here, keep to the steps outlined below: Table 8-1 Originally configured module 6GK7 343−1CX00−0XE0 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Configuration Steps Case a: Configuration unchanged...
  • Page 46: Further Notes On Operation

    In STEP 7 / NCM Diagnostics with Operating Mode S Factory defaults reset In STEP 7 / NCM Diagnostics with Operating Mode Defaults B3L−46 Clear/Reset " Clear/Reset Module " Reset to Factory " CP 343-1 Lean for Industrial Ethernet / Manual Part B3L C79000-G8976-C198-04 Release 03/2007...
  • Page 47: Working With Fast Ethernet − Automatic Switchover

    CP, “Port Parameters” tab. Autocrossing The automatic setting also includes an “autocrossing” mechanism. With autocrossing, you can connect network components and end devices using either crossover or straight−through cables. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 B3L−47...
  • Page 48 “100 Mbps − half duplex”. Reason: Due to the fixed setting, no autonegotiation response is possible; the connected partner recognizes the 100 Mbps with autosensing but nevertheless remains in half duplex. B3L−48 CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 49: Snmp Agent

    S Write access is permitted only for the following MIB objects: sysContact, sysLocation and sysName; For security reasons, only read access is permitted for all other MIB objects. S Traps are not supported by the CP. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 B3L−49...
  • Page 50: Possible Security Gaps On Standard It Interfaces / Preventing Illegal Access

    If you have questions on the use of firewall systems and IT security, please contact your local Siemens office or representative. You will find the address in the SIMATIC catalog IK PI or on the Internet at http://www.automation.siemens.com/net...
  • Page 51: B3L−51

    The following local port numbers are reserved; You should not use these for other purposes in the connection configuration. Table 9-1 Reserved Port Numbers Protocol CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 Port number 20, 21...
  • Page 52: Restart After Detection Of A Duplicate Ip Address In The Network

    GSDML file You will find the GSDML file for the CP described here on the Internet under the following entry ID: http://support.automation.siemens.com/WW/view/en/19698639/133100 B3L−52 > “FAQ” tab CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 53: 10 How To Load New Firmware

    In this case, turn the station off and on again and repeat the download. CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04...
  • Page 54: B3L−54

    CL. 1, Zone 2, GP.IIC. T.. Ta:.. AS/NZS 2064 (Class A). EN 61000−6−2, EN 61000−6−4 (replaces EN 50081−2) EN60079−15 II 3 G EEx nA II T.. KEMA 03 ATEX 1228 X CP 343-1 Lean for Industrial Ethernet / Manual Part B3L C79000-G8976-C198-04 Release 03/2007...
  • Page 55 Data” /1/ in the chapter “General Technical Specifications” applies to the CP. S Electromagnetic compatibility S Transportation and storage conditions S Mechanical and climatic ambient conditions S Insulation tests, class of protection and degree of protection CP 343-1 Lean for Industrial Ethernet / Manual Part B3L Release 03/2007 C79000-G8976-C198-04 B3L−55...
  • Page 56: Release 03/2007 C79000-G8976-C198-04

    11 Technical Specifications CP 343-1 Lean for Industrial Ethernet / Manual Part B3L B3L−56 Release 03/2007 C79000-G8976-C198-04...