Operation

7.4 Automatic mode - programming of the electronic module (3KC8 only)

7.4
Automatic mode - programming of the electronic module (3KC8
only)
The electronic module of the 3KC8 of the transfer switching equipment can be programmed
directly on the module in five steps. Programming is described below.
Figure 7-16
7.4.1

Step 1: Preset network conditions

You set the defaults of the network conditions on the DIP switches. A screwdriver is required
for this. First, make sure the transfer switching equipment is in manual operation.
1. Check whether the transfer switching equipment is in the "Manual" position. Set the
transfer switching equipment to the "Manual" position if applicable.
Figure 7-17
132
Electronic module
Set the switch to the "Manual" position
Manual, 08/2017, L1V30368969104A-02