Reactor Leak Check - GE Sievers InnovOx Operation And Maintenance Manual

On-line toc analyzer
Hide thumbs Also See for Sievers InnovOx:
Table of Contents

Advertisement

Chapter 9: Troubleshooting

Reactor Leak Check

This test checks for leaks in the same area as the Reactor Bypass Leak Check, and it also checks for leaks at the
reactor tube. These areas are highlighted in Figure 73.
Press the Reactor button to start the test.
The following valves are closed: V1-R, V3-R, V6-R, V7-R and V7-SH.
Valves V2-R, V4-R and V5-R are opened.
The Gas Control Module pressurizes the lines using the optional air pump P1-GS or the pressurized gas
source for 10 sec., then valve V2-GS closes to trap that pressure in the area being tested. During this
10-sec. pressurization period, the timer remains at 00:00.
Monitor the pressure appearing on the right side of the display. Note the pressure at time = 00:00, then
note the pressure 30 sec. later (time = 00:30).
Press the Reactor Valve button to stop the test.
The pressure should not have dropped more than 3 psia. If the pressure did drop more than that
amount, but it passed the previous leak check, then check the O-rings on the seals in V4-R and V5-R.
Replace the seals if necessary. If the seals are good, then check the reactor tube fittings on V4-R and
V5-R. A hole in the reactor will cause a leak also.
Remove the plug on the NDIR end cap outlet gas line if this is the last leak test to be performed.
Otherwise, leave the plug in place and proceed to the next leak test.
GE Analytical Instruments ©2013
202 of 238
DLM 68100-06 EN Rev. A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents