Description of Functions and Constants

2-8-17 Overtorque Detection Function

Item name
Overtorque detection level
Overtorque detection time
Overtorque detection signal
Overtorque detection selection
56
Constant to be set
No. 38
No. 39
No. 34 and No. 35
No. 37
When an excessive load is placed on the machine, the increase in
motor current is detected and alarm signal can be output.
If the current exceeds the value set in No. 38 for longer than the
time limit set in No. 39, the overtorque detection signal is output to
control circuit terminal 13 or 14 until the current falls below the
value set in No. 38.
To output the signal to control circuit terminal 13, set constant No.
34 to 4. To output the signal to control circuit terminal 14, set con-
stant No. 35 to 4.
Motor current
No. 38
Overtorque
detection signal
ON
No. 39
The second digit of No. 37 determines whether overtorque will be
detected during acceleration and deceleration, and the third digit
determines whether overtorque will be treated as a fault (OL3) or
operation will continue after overtorque is detected.
No. 37 = x001
st
1
digit
0: Overtorque detection disabled
1: Overtorque detection enabled
nd
2
digit
0: Detection only at steady speed
1: Detection during accel/decel also
rd
3
digit
0: Operation after overtorque detection
1: Output shut off after overtorque detection
160%
0.1 s
No. 34 = 0, No. 35 = 1
0000
Time
ON
No. 39
Section 2-8
Factory preset