Connecting The Motor To The Inverter In A Star Or Delta Connection - Siemens SINAMICS G12 Hardware Installation Manual

Pm240-2 power modules, ip20 / push-through technology (pt)
Table of Contents

Advertisement

Connecting-up

5.4 Connecting the motor to the inverter in a star or delta connection

5.4
Connecting the motor to the inverter in a star or delta connection
Standard induction motors with a rated power of approximately ≤ 3 kW are normally connected
in a star/delta connection (Y/Δ) at 400 V/230 V. For a 400‑V line supply, you can connect the
motor to the inverter either in a star or in a delta connection.
Operating the motor in a star connection
Operating the motor in a delta connection with 87 Hz characteristic
The motor only goes into field weakening above 87 Hz.
The higher motor power when operated with an 87 Hz characteristic has the following
disadvantages:
● The inverter must supply approximately 1.73x current. Select an inverter based on its rated
current - and not its rated power.
● The motor temperature increases more significantly than when operated with f ≤ 50 Hz.
● The motor must have windings that are approved for a voltage > rated voltage U
● As the fan impeller rotates faster, the motor has a higher noise level than operation with
f ≤ 50 Hz.
66
In a star connection, the motor can provide its
rated torque M
in the range 0 ... rated frequen‐
N
cy f
.
N
Rated voltage U
= 400 V is available at a rated
N
frequency f
= 50 Hz.
N
The motor goes into field weakening above the
rated frequency. In field weakening, the availa‐
ble motor torque decreases linearly with 1/f. In
field weakening, the available power remains
constant.
In a delta connection, the motor is oper‐
ated with a voltage and frequency above
its rated values. As a consequence, the
motor power is increased by a factor
√3 ≈ 1.73.
In the range f = 0 ... 87 Hz, the motor can
output its rated torque M
The maximum voltage U = 400 V is avail‐
able at a frequency of f = √3 × 50 Hz ≈
87 Hz.
Hardware Installation Manual, 08/2017, A5E33294624B AG
.