Connecting the motor to the inverter in a star or delta connection

Standard induction motors with a rated power of approximately ≤ 3 kW are normally
connected in a star/delta connection (Y/Δ) at 400 V/230 V. For a 400-V line supply, you can
connect the motor to the inverter either in a star or in a delta connection.
Operating the motor in a star connection
78
Control Unit motor and power connections
In a star connection, the motor can provide its
rated torque M
in the range 0 ... rated fre-
N
quency f
.
N
Rated voltage U
= 400 V is available at a
N
rated frequency f
N
The motor goes into field weakening above
the rated frequency. In field weakening, the
available motor torque decreases linearly with
1/f. In field weakening, the available power
remains constant.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
= 50 Hz.