RH2288H V3 Server
User Guide
Figure 3-2 Direction of heat dissipation
3.2.2 Temperature and Humidity Requirements
To ensure continued safe and reliable equipment operating, install or position the
system in a well-ventilated, climate-controlled environment.
●
●
●
Table 3-1 Temperature and humidity requirements in the equipment room
Item
Temperature
Relative humidity (RH,
non-condensing)
3.2.3 Cabinet Requirements
The cabinet must meet the following requirements:
●
●
Issue 46 (2022-12-28)
Use temperature control devices all year long in any climates.
In dry areas, use humidifiers to ensure ambient humidity.
In humid areas, use dehumidifiers.
A standard 19-inch cabinet with a depth of more than 1000 mm (39.37 in.).
Complies with International Electrotechnical Commission 297 (IEC 297).
Copyright © Huawei Technologies Co., Ltd.
3 Installing and Removing the RH2288H V3
Description
5°C to 40°C (41°F to 104°F)
8% to 90%