RH2288H V3 Server
User Guide
Figure 3-1 Installation process
3.2 Installation Environment
Before installing the server, check that the cabinet, space, temperature, and
humidity meet installation requirements.
3.2.1 Space and Airflow Requirements
To allow for servicing and adequate airflow, observe the following space and
airflow requirements:
●
●
●
●
●
The server draws in cool air from the front of the cabinet and exhausts hot air
from the rear. Therefore, the front and rear of the cabinet must be well ventilated
for optimal heat dissipation.
Issue 46 (2022-12-28)
Install the RH2288H V3 in an access-restricted area.
Keep the area in which the server is located clean and tidy.
For easy heat dissipation and maintenance, keep a clearance of 800 mm
(31.50 in.) between walls and the front and rear doors of the cabinet.
Do not block the air intake vents. Otherwise, air intaking and heat dissipation
will be affected.
Ensure that the air conditioning system in the equipment provides enough
wind to ensure proper heat dissipation of all components.
Copyright © Huawei Technologies Co., Ltd.
3 Installing and Removing the RH2288H V3
Figure 3-2
shows the direction of heat dissipation.
81