8.2
Power Supply Wiring to the GOT
The following shows the examples of wiring the power cable, ground cable and other cables to the GOT power supply
terminal.
INPUT
24VDC
-
Ground cable
Grounding
Precautions
■Treatment on power cables
For 24 V DC cables, use thick wires as much as possible (Cable cross section: 0.75 mm
them to the terminals.
To prevent a short circuit due to loose screws, use a solderless terminal with an insulation sleeve.
■Grounding
After connecting the FG terminal, make sure to connect it to the ground.
Otherwise, the system is susceptible to noise.
8 WIRING OF POWER SUPPLY SECTION
88
8.2 Power Supply Wiring to the GOT
GOT
+
Fuse
2
2
to 2 mm
), and make sure to twist