Conforming standards in the EMC Directive

The GOT complies with the following standards in the EMC Directive.
Applied
Test standard
standard
EN61131-2:
CISPR16-2-3
2007
Radiated noise
CISPR16-2-1
Conducted noise
IEC61000-4-2
Electrostatic immunity
IEC61000-4-3
Radiated electromagnetic field,
amplitude modulation
IEC61000-4-4
Fast transient burst noise
IEC61000-4-5
Surge immunity
IEC61000-4-6
Conducted RF immunity
IEC61000-4-8
Power supply frequency magnetic
field immunity
*1 The GOT is an open type device (designed to be integrated in equipment).
Make sure to install the GOT on a control panel.
This test item is conducted in the condition where the GOT is installed on a control panel and combined with the MITSUBISHI
ELECTRIC PLC.
*2 The length of a sound output cable must be 30 m or less.
*3 QP: Quasi-peak value, Mean: Average value
*4 This test item is conducted in the following conditions.
30 MHz to 230 MHz
QP: 40 dBμV/m (measured at 10 m)
230MHz to 1000MHz
QP: 47 dBμV/m (measured at 10 m)
6 EMC DIRECTIVE
54
6.1 Overview
Test details
Test for measuring electromagnetic emissions
*1*2
from the product
Test for measuring electromagnetic emissions
*1*2
from the product to the power cables
Immunity test in which static electricity is applied
*1*2
to the cabinet of the equipment
Immunity test in which an electric field is applied
to the product
*1*2
Immunity test in which burst noise is applied to the
*1*2
power cables and the signal lines
Immunity test in which lightening surge is applied
*1*2
to the product
Immunity test in which a noise inducted on the
*1*2
power cable and the signal lines is applied
Test for checking normal operations under the
circumstance exposed to the ferromagnetic field
*1*2
noise of the power supply frequency (50/60 Hz)
Standard value
• 30 MHz to 230 MHz
QP: 30 dBμV/m (measured at 30 m)
• 230MHz to 1000MHz
QP: 37 dBμV/m (measured at 30 m)
• 150kHz to 500kHz
*3
QP: 79dB, Mean: 66dB
• 500kHz to 30MHz
*3
QP: 73dB, Mean: 60dB
• Contact discharge: ±4 kV
• Aerial discharge: ±8 kV
80 MHz to 1000 MHz: 10 V/m
1.4GHz to 2GHz: 3V/m
2.0GHz to 2.7GHz: 1V/m
(80% amplitude modulation at 1 kHz)
Power cable: 2kV
Digital I/O: 1 kV
Analog I/O: 1 kV
Signal cable: 1kV
• DC power type
Power cable (between cable and ground):
±0.5kV
Power cable (between cables): ±0.5kV
Data communication port: ±1 kV
Power cable: 10V
Data communication port: 10 V
30 A/m
*3*4
*3*4