19.1

Power Supply Wiring

Connect the power supply to the power terminals on the back panel of the GOT.
Use a specified size power supply wire to prevent voltage drop, and tighten the terminal screws firmly to a specified torque.
Do not exceed the number of wires that are allowed to be connected.
Secure the wires to prevent stress from being directly applied to the terminal block or wire connections.

Cable types and wire end processing

Process the end of the electrical wire (solid or stranded), or attach a ferrules with plastic sleeve to the wire end.
Terminal screws should be tightened to between 0.5 to 0.6 N·m. Terminal screws must be secured to prevent a loose
connection thus avoiding a malfunction.
Do not tighten the terminal screws with a torque outside the specified range. Failure or malfunction may result.
Electrical wire size
Electrical wire size
Solid wire
2
0.5 to 2.5 mm
AWG20 to AWG14
Wire end processing
■Connecting the wire directly
Twist the end of the stranded wire. Make sure there are no wire whiskers.
Do not solder the wire end.
Approx. 6 mm
■Using a ferrules with plastic sleeve to connect the wire
A wire with a too thick of a wire sheath may not fit the insulation sleeve. Refer to the outline drawing for how to select the
proper size wire.
Insulation sleeve
2.8 to 4.2 mm
8 to 12 mm
14 to 18 mm
Manufacturer
Phoenix Contact Inc.
19 WIRING
170
19.1 Power Supply Wiring
Stranded wire
0.5 to 2.5 mm
AWG20 to AWG14
Terminal
contact
section
Model
AI 0.75-8GY (0.5 to 0.75 mm
AI 1.0-8RD (0.75 to 1.0 mm
AI 1.5-8BK (1.0 to 1.5 mm
AI 2.5-8BU (1.5 to 2.5 mm
2
2
)
2
)
2
)
2
)
Ferrules with plastic sleeve
2
0.5 to 2.5 mm
AWG20 to AWG14
Crimper type
CRIMPFOX UD6

Advertisement