Mitsubishi Electric GOT SIMPLE Series Operation Manual page 317

Hide thumbs Also See for GOT SIMPLE Series:
Table of Contents

Advertisement

Data to be backed up and restored
The following shows data to be backed up and restored.
Data other than the following data cannot be backed up and restored.
■Basic model QCPU
Item
Parameter
Intelligent function module parameter
Sequence program
SFC program
*1
File register
Device comment
Device initial value
*1 The file register in the Flash card installed in the CPU is always restored without confirming saving.
Select whether restoring or not the file register stored in the SRAM card or standard RAM in the dialog box displayed when restoration is
executed.
When the file register is not restored, the existing file register is deleted.
Therefore, programs of the controller may not work normally.
If a problem occurs in the operation of the controller after restoration, perform the restoration again, including to the file register.
■High Performance model QCPU
Item
Parameter
Intelligent function module parameter
Program
Device comment
Boot operation specification file
Device initial value
*1
File register
*2
Sampling trace file
*2
Failure history data
Programmable controller user data
*1 The file register in the Flash card installed in the CPU is always restored without confirming saving.
Select whether restoring or not the file register stored in the SRAM card or standard RAM in the dialog box displayed when restoration is
executed.
When the file register is not restored, the existing file register is deleted.
Therefore, programs of the controller may not work normally.
If a problem occurs in the operation of the controller after restoration, perform the restoration again, including to the file register.
*2 The item can be backed up only.
Description
Parameter for operating a programmable controller
Parameter for intelligent function modules
Program that the CPU operates
Sequence program with the SFC programming format
Data stored in file registers
Device comment to be stored in a programmable controller
Setting the device initial value
Description
Parameter for operating a programmable controller
Parameter for intelligent function modules
Program that the CPU operates (Including SFC program)
Device comment to be stored in a programmable controller
Batch file for starting programs stored in ROM and others
Setting the device initial value
Data stored in file registers
Sampling trace data that the specified device data is continuously collected
with the specified timing
Failure history data that are recorded self-diagnostic results
Any user-created data stored in a memory card
27 CONTROL OF VARIOUS DATA (DATA CONTROL)
27.8 BACKUP/RESTORE
File name
PARAM.QPA
IPARAM.QPA
MAIN.QPG
MAIN-SFC.QPG
MAIN.QDR
MAIN.QCD
MAIN.QDI
File name
PARAM.QPA
IPARAM.QPA
***.QPG
***.QCD
AUTOEXEC.QBT
***.QDI
***.QDR
***.QTD
***.QFD
***.*** (Optional)
315
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gs25Gs21

Table of Contents