18.3
Mounting Position
When mounting the GOT, the following clearances must be maintained from other structures and devices.
For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward.
Unit: mm (inch)
Installation environment
In the presence of radiated-noise or heat-
generating equipment nearby
In the absence of radiated-noise or heat-
generating equipment nearby
Horizontal installation
B
C
A
Vertical installation
D
B
C
A, D
B
50 (1.97) or more
Horizontal: 80 (3.15) or
more
Vertical: 50 (1.97) or
more
20 (0.79) or more
20 (0.79) or more
D
A
C
Horizontal: 50 (1.97) or
more
Vertical: 80 (3.15) or
more
20 (0.79) or more
E
Panel thickness: 1.6 to 4 mm
(0.06 to 0.16)
E
Panel thickness: 1.6 to 4 mm
(0.06 to 0.16)
E
100 (3.94) or more
20 (0.79) or more
18 INSTALLATION
165
18.3 Mounting Position
18