18.2
Panel Cutting Dimensions
Cut holes in the following dimensions on the panel.
Ensure 10 mm of space in upper and lower parts of the panel for mounting fixtures.
For the vertical installation, install the GOT so that the vertical installation arrow printed on the GOT rear face points upward.
Horizontal
Unit: mm (inch)
Model
GS2110-WTBD-N
GS2110-WTBD
GS2107-WTBD-N
GS2107-WTBD
Dimension C is required for installing fittings on the control panel.
18 INSTALLATION
164
18.2 Panel Cutting Dimensions
A
A
258 (10.16)
(+2 (0.08), 0 (0))
191 (7.52)
(+2 (0.08), 0 (0))
C
Vertical
B
C
200 (7.88)
10 (0.39) or more
(+2 (0.08), 0 (0))
137 (5.40)
10 (0.39) or more
(+2 (0.08), 0 (0))
B
C
Panel thickness
1.6 (0.06) to 4 (0.16)
1.6 (0.06) to 4 (0.16)