4.1

Setting up the system unit and the peripherals

4.1.1

Setting up the system unit

When setting up the system unit, make sure
... that there is enough room to perform maintenance, diagnostic and
upgrading work (150 cm on left, 20 cm on right, 60 cm at rear).
... that the rear of the system unit is freely accessible, as the peripherals need
to be connected to the backplane.
... that the front of the system unit is freely accessible and that none of the air
vents are obstructed.
... that the rear of the unit is at least 50 cm from the wall to allow warm air to
pass out without hindrance.
... that the power plugs can be reached easily and without risk and that the
rated voltage specified on the devices ID plate is the same as the local line
voltage.
... that the device is protected from direct sunlight.
... that the required environmental conditions (see chapter "Technical data" on
page 145) are maintained at all times.
... that the stabilizers are mounted to ensure the stability of the system cabinet.
4.1.2

Setting up the monitor

For instructions on setting up your monitor you should refer to the operating manual
that came with the device.
4.1.3

Setting up the peripherals cabinet

The peripherals cabinet is set up and installed solely by SNI service personnel.