PTX10001-36MR Clearance Requirements for Airflow and Hardware
Maintenance
When planning the site for a PTX10001-36MR installation, you must allow sufficient clearance around
the installed chassis (see
Figure 19: Clearance Requirements for Airflow and Hardware Maintenance for a PTX10001-36MR
Follow these guidelines:
• For the cooling system to function properly, the airflow around the chassis must be unrestricted. See
"PTX10001-36MR Cooling System" on page 21
chassis.
• If you are mounting a PTX10001-36MR in a rack with other equipment, ensure that the exhaust from
other equipment does not blow into the intake vents of the chassis.
• You must leave at least 24 in. (61 cm) both in front of and behind the PTX10001-36MR for service
personnel to remove and install hardware components. You must leave adequate space at the front
and back of the PTX10001-36MR. NEBS GR-63 recommends that you allow at least 30 in. (76.2 cm)
in front of the rack or cabinet and 24 in. (61 cm) behind the rack.

PTX10001-36MR Physical Specifications

Table 23 on page 53
lists the physical specifications for the PTX10001-36MR chassis.
Figure 19 on page
52).
for more information about the airflow through the
52