The fan modules in a PTX10001-36MR are hot-removable and hot-insertable field-replaceable units
(FRUs)—you can remove and replace them without powering off the PTX10001-36MR or disrupting
routing functions.
To install a fan module in a PTX10001-36MR:
1. To prevent damage to the equipment caused by static discharge, attach an electrostatic discharge
(ESD) grounding strap to your bare wrist, and connect the strap to one of the ESD points on the
chassis.
2. Taking care not to touch the connectors, remove the fan module from its bag.
3. Align the module with the open slot on the FRU end of the PTX10001-36MR and slide it in until it is
fully seated.
4. Using the Phillips screwdriver, tighten the locking screw (3 or 4 turns). See
Figure 41: Install a Fan Module in a PTX10001-36MR