PTX10001-36MR Chassis Grounding Cable and Lug Specifications

For installations that require a separate grounding conductor to the chassis, the PTX10001-36MR must
be adequately grounded before power is connected to ensure proper operation and to meet safety and
electromagnetic interference (EMI) requirements. To ground a PTX10001-36MR, connect a grounding
cable to earth ground and then attach it to the chassis grounding points.
WARNING: The device is a pluggable type A equipment installed in a restricted-access
location. It has a separate protective earthing terminal provided on the chassis in
addition to the grounding pin of the power supply cord. This separate protective
earthing terminal must be permanently connected to earth ground for installations that
require a separate grounding conductor to the chassis.
WARNING: To comply with GR-1089 requirements, all intrabuilding copper cabling
used for transceiver ports must be shielded and grounded at both ends.
CAUTION: Before device installation begins, a licensed electrician must attach a cable
lug to the grounding cables that you supply. See
Ground" on page
PTX10001-36MR.
Before connecting the PTX10001-36MR to earth ground, review the following information:
• The grounding lug required is a Panduit LCD6-14AH-L or equivalent (not provided).
• The grounding cable that you provide for a PTX10001-36MR must be the same size or heavier than
the input wire of each power supply. Minimum recommendations are 8 AWG (8.4 mm²) stranded
wire, 90° C wire, or as permitted by local code.
86. A cable with an incorrectly attached lug can damage the
"Connect the PTX10001-36MR to