SmartLinx ® Parameters (P790 to P792)
These parameters are specific to the SmartLinx® module installed. Refer to the
module documentation for a list and description of the specific parameter
requirements.
P790 Hardware Error
Use this feature to display the results of ongoing hardware tests within the
communications circuitry. If any test does not meet the PASS requirements,
communication halts and tests are repeated until PASS requirements are met.
Communications then resumes.
Displays:
PASS:
FAIL:
ERR1:
P791 Bus Error
This feature indicates if an error condition is occurring on the bus.
Displays:
0 = no error
Ø = error code, refer to the SmartLinx module documentation for explanation of
P792 Bus Error Count
This register increments by 1 each time a bus error (P752) is reported. The
resister is factory set at 0 and can be preset to any value. The register is reset to 0
by the master reset (P999).

Echo Processing Parameters (P800 to P807)

P800 Near Blanking
Use this feature if the material level is incorrectly reported to be near the
transducer face.
Near Blanking may be extended to overcome measurement difficulties which
cannot otherwise be corrected by transducer location, mounting, or aiming
modification. Extend Near Blanking to 150 mm (6 in) beyond the incorrect
distance measured.
This parameter is preset to 1.000 m or equivalent Units (P005) regardless of
Empty (P006).
Note:
Ensure the Near Blanking distance is less than Empty (P006) - Span (P007).
To reset the automatic Near Blanking value press
Values:
7ML19981BC01
no problem
faulty SmartLinx module or DPS300
unknown protocol, upgrade the DPS300 software
the error code
0.000 to 9999 (preset 1.00m)
81
.
InterRanger DPS300