Wiring and Fitting
5.4.3
Wiring Terminal Modules with Fast Connect
Features
S In the case of terminal modules with Fast Connect, the individual wires are
attached using a quick connection method that requires no stripping.
S Fast Connect is a connection method that requires no preparation (i.e. the
conductor does not have to be stripped).
S Each terminal of the terminal module with Fast Connect has a test opening (for
measuring the voltage, for example). The test opening is suitable for test
probes with a maximum diameter of
S Wire end ferrules are not permitted.
S Diagram of the Fast Connect terminal module
Fast Connect
terminal module
Figure 5-4
Requirements
Adhere to the wiring rules.
Tool Required
3-mm screwdriver
5-10
Opening for measuring, checking: max.
Opening for 1 conductor: 0.5 mm to 1.5 mm
Locking mechanism open (the cable can be inserted)
Locking mechanism closed (the cable is connected)

Block Diagram of the Terminal Module with Fast Connect

1.5 mm.
1.5 mm
2