Analog Electronic Modules
Measuring Range for Thermocouple Type T
Table 12-22 SIMATIC S7 Format: Measuring Range Type T in °C and °F
Units
Type T
in 5C
Dec.
Hex.
> 540.0
32767
7FFF
540.0
5400
1518
H
:
:
:
400.1
4001
0FA1
400.0
4000
0FA0
:
:
:
–270.0
–2700
F574
< –270.0
–32768
8000
H
12.1.3
Analog Value Representation for the Measuring Ranges of the
Analog Output Modules in SIMATIC S7 Format
Introduction
The tables in this section contain the digitized analog values for the measuring
ranges of the analog output modules.
The binary representation of the analog values is always the same, so these tables
only compare the output ranges and the units.
12-18
Units
Type T
in 5F
Dec.
> 1004.0
32767
7FFF
H
1004.0
10040
2738
752.1
7521
1DC1
H
752.0
7520
1D60
H
:
:
:
–454.0
–4540
EE44
H
< –454.0
–32768
8000
Range
Hex.
Overflow
H
H
Overrange
H
H
Rated range
H
Underflow
H
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07