Siemens ET 200S Manual page 148

Distributed i/o system
Hide thumbs Also See for ET 200S:
Table of Contents

Advertisement

Commissioning and Diagnostics
Evaluating Hardware Interrupts with STEP 7
In the event of a hardware interrupt, the CPU interrupts the processing of the user
program and processes the process interrupt block OB 40 instead.
The module channel that triggered the hardware interrupt is entered in the start
information of OB 40 in the OB40_POINT_ADDR variable. In the figures below you
will find the assignment to the bits of the local double word 8.
Hardware Interrupts in the Case of:
2DI 24 VDC High Feature and 4DI 24 VDC High Feature Electronic Modules:
LB 8
31 30 29 28 27 26
1
1
Rising edge: Channel 2
Rising edge: Channel 3
Figure 6-18
Start Information of OB 40: Which Event Triggered a Hardware Interrupt with Digital Input
Modules
Hardware Interrupts with:
2AI U High Speed, 2AI I 2WIRE High Speed, and 2AI I 4WIRE High Speed
Electronic Modules:
LB 8
31 30 29 28 27 26
25 24
Figure 6-19
Start Information of OB 40: Which Event Triggered a Hardware Interrupt with Analog Input
Modules
You will find a description of the OBs 40 in the Reference Manual System and
Standard Functions.
6-24
LB 9
LB 10
25 24
1
1
Rising edge: Channel 0
Rising edge: Channel 1
LB 9
23 22 21 20 19 18
17 16
1
1
1
Upper limit value violated: Channel 1
Lower limit value violated: Channel 0
Upper limit value violated: Channel 1
LB 11
1
Bit no.
0
LD 8
2DI
4DI
LB 10
LB 11
1
0
1
Lower limit value violated: Channel 0
Distributed I/O System ET 200S
Bit no.
LD 8
EWA 4NEB 780 6024-02 07

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7 151-1aa00-8xa0

Table of Contents