Table 13-4 Enhanced Control Interface
Address
Byte 2
Byte 3
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Assignment
Specify sensitivity/distance value on
channel 2
S
Bit 0:
Bit 0:
1: Transfer sensitivity/distance value to the
sensor on channel 2
(using rising edge)
0: Deactivated
S S
Bit 1 to bit 7:
Sensitivity/distance value
on channel 2: 1 to 126 (depending on the
sensor)
Teach-in on channel 2
S
Bit 0:
1: Start teach-in on the sensor on channel 2
(at the rising edge)
0: Deactivated
S
Bit 1 to bit 7: 0
Specify sensitivity/distance value on
channel 3
S
Bit 0:
Bit 0:
1: Transfer sensitivity/distance value to the
sensor on channel 3
(using rising edge)
0: Deactivated
S S
Bit 1 to bit 7:
Sensitivity/distance value
on channel 3: 1 to 126 (depending on the
sensor)
Teach-in on the sensor on channel 3
S
Bit 0:
1: Start teach-in on the sensor on channel 3
(at the rising edge)
0: Deactivated
S
Bit 1 to bit 7: 0
4 IQ-SENSE
Designation on
"IQ-SENSE Opto" FB
WR_TEACH_VAL
TEACH_VAL_IN
START_TEACH
WR_TEACH_VAL
WR_TEACH_VAL
TEACH_VAL_IN
START_TEACH
13-13