Hardware Interrupt
This parameter allows you to enable or disable hardware interrupts. Hardware
interrupts are only supported when the ET 200S is in DPV1 mode.
Insert/Remove-Module Interrupt
This parameter allows you to enable or disable insert/remove-module interrupts.
Insert/remove-module interrupts are only supported when the ET 200S is in DPV1
mode.
Analog Value Format
Here you set the number format for all analog electronic modules.
Interference Frequency Suppression
The frequency of your alternating voltage system can affect measured values
negatively, particularly in the case of both measurements in small voltage ranges
and thermocouples. Specify here the dominant line frequency in your system
(50 Hz or 60 Hz).
The interference frequency suppression parameter is valid for all analog electronic
modules. The integration time and conversion time of the individual modules are
also set by means of this parameter. See the technical specifications of the analog
electronic modules in Chapter 12.
Reference Junction Slot 1 to 8
See Section 12.2.2
Reference Junction Input 1 to 8
See Section 12.2.2
Synchronize DP Slave with DP Cycle
You can use this parameter to enable or disable clocking.
If you enable clocking, the I/Os of the ET 200S are synchronized with the global
control frame of the master (as an equidistance clocking).
Prerequisites: See Section 3.6.
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Interface Modules
8-5