RESERVE
Order Number
6ES7 138-4AA00-0AA0 (installation width 15 mm)
6ES7 138-4AA10-0AA0 (installation width 30 mm)
Features
The RESERVE module has the following characteristic features:
S Suitable for all TM-E terminal modules (installation widths 15 mm and 30 mm)
S Reserves a slot for any electronic module slot. Insert the RESERVE module in
the reserved slot of the ET 200S configuration.
Note
S
Note the following in the IM 151 (as of 6ES7 151-1AA01-0AB0), IM 151 FO
and IM 151/ CPU:
If you remove an electronic module from the ET 200S during operation and
insert a reserve module in its place, you must then switch the supply voltage to
the interface module OFF and ON.
S
Note with the IM 151 (6ES7 151-1AA00-0AB0):
The reserve module cannot be used in the ET 200S.
Parameter Assignment
S In STEP 7 or COM PROFIBUS, parameterize the electronic module you want
to use for future applications, such as 4DI DC High Feature on the slot of the
RESERVE module.
– Drag the module to the configuration table
– Set the parameters
Distributed I/O System ET 200S