Siemens ET 200S Manual page 144

Distributed i/o system
Hide thumbs Also See for ET 200S:
Table of Contents

Advertisement

Commissioning and Diagnostics
1SI 3964/ASCII, 1SI Modbus/USS Serial Interface Modules
SF
Group
error (red)
TX
RX
Status indicator
Figure 6-16
LEDs on the 1SI 3964/ASCII, 1SI Modbus/USS
6-20
LEDs
SF TX
RX
On
Hardware fault
Firmware error
Parameter assignment
error
Wire break or loose
cable between the mo-
dule and the communi-
cation partner
Communication error
On
The module is sending
data via the interface.
On
The module is receiving
data via the interface.
1
Only detected in the case of RS-422 interface connections when the
default for the receive line is set to R(A) 5V/R(B) 0V.
Meaning
What to Do
Check the module
Check the parameteriza-
tion. Evaluate the diagno-
sis.
Check the wiring.
1
Check the communication
settings.
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07