6.6.4
Master PROFIBUS Address
Definition
The master PROFIBUS address diagnostic byte contains the PROFIBUS address
of the DP master that:
S Assigned parameters to the DP slave and
S Has read and write access to the DP slave
The master PROFIBUS address is in byte 3 of the slave diagnosis.
6.6.5
Manufacturer ID
Definition
The manufacturer ID contains a code that describes the type of the DP slave.
Manufacturer ID
Table 6-11 Structure of the Manufacturer ID (Bytes 4, 5)
Byte 4
80
H
80
H
80
H
80
H
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Byte 5
F3
ET 200S with IM151-1 BASIC
H
6A
ET 200S with IM151-1 STANDARD
H
6B
ET 200S with IM151-1 FO STANDARD
H
E0
ET 200S with IM151-1 HIGH FEATURE
H
Commissioning and Diagnostics
Manufacturer ID for
6-33