Table 6-18 1Count 5V/500kHz
Error Type
16
10000: Parameter
D
assignment error
26
11010: External fault
D
1STEP 5V/204kHz
Table 6-19 EM 1STEP 5V/204kHz
Error Type
1
00001: Short circuit
D
9
01001: Error
D
16
10000: Parameter
D
assignment error
2PULSE
Table 6-20 2PULSE
Error Type
1
00001: Short circuit
D
9
01001: Error
D
16
10000: Parameter
D
assignment error
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Meaning
Parameters have not been
assigned to the module.
Wire break/short circuit of the 5
V sensor signals:
A, /A, B, /B, N, /N,
Meaning
Short circuit of the sensor
supply.
Internal module error occurred.
Parameters have not been
assigned to the module.
Meaning
Short circuit of the sensor
supply or the actuator.
Internal module error occurred.
Parameters have not been
assigned to the module.
Commissioning and Diagnostics
What to Do
Adjust the parameter
assignment.
Correct the parameter
assignment.
What to Do
Check the wiring to the
switches. Correct the process
wiring.
Replace the module.
Adjust the parameter
assignment.
What to Do
Check the wiring to the
momentary-contact switches
and the actuators. Correct the
process wiring.
Replace the module.
Adjust the parameter
assignment.
6-45