Power Modules
Technical Specifications
Dimensions and Weight
Dimensions W H D
(mm)
Weight
Voltage, Currents, Potentials
Rated load voltage
S
Overvoltage protection
Max. current-carrying
capacity
S
For 24–56.7 VDC
S
For 24–48/120/230 VAC Up to 30 °C:
S
Short-circuit protection
Isolation
S
Between rated load
voltage and backplane
bus
S
Between the
power modules
Insulation tested with
Current consumption
From the backplane bus
S
From load voltage L1/L+
(no load)
Power dissipation of the
module
10-10
15 81 52
Diagnostic function
S
34g
S
S
24–56.7 VDC
S
24–48 VAC/
120–230 VAC
Yes
1
10 A
Up to 30 °C:
max. 10 A
Up to 40 °C:
max. 9 A
Up to 60 °C:
max. 7 A
max. 8 A
Up to 40 °C:
max. 7 A
Up to 60 °C:
max. 5 A
Yes, IEC 127-2/1,
250 V, 10 A, fast
fuse (5 x 20 mm),
1
replaceable
Yes
Yes
4000 VDC
Max. 9.5 mA
Max. 9 mA
Max. 5 W
Status, Interrupts, Diagnostics
Group error
Load voltage monitoring
Fuse
Diagnostic information
can be displayed
The fuses on this module are only additional
fuses. External overcurrent protection (suitable
for branch circuits in accordance with the
applicable national regulations for electrical
engineering) is required in the supply lines of the
load circuit.
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Yes
Red "SF" LED
Green "PWR" LED
Green "FSG" LED
Yes