Analog Electronic Modules
12.15
2AI TC Standard Analog Electronic Module
(6ES7 134-4JB00-0AB0)
Order Number
6ES7 134-4JB00-0AB0
Features
S 2 inputs for thermocouple or voltage measurement
S Input ranges:
– Voltage measurement:
– Thermocouples: type E, N, J, K, L, S, R, B, T, resolution 15 bits + sign
S Isolated from the load voltage L+
S Linearization of the sensor characteristic curves
S Permitted common-mode voltage 2 VAC
Terminal Assignment
The following table indicates the terminal assignment of the 2AI TC Standard for
the different terminal modules:
Voltage measurement as for 2AI U Standard (see Section 12.5).
Table 12-87 Terminal Assignment of the 2AI TC Standard
View
CH0
M
0+
1
5
M
0–
2
6
M
ana
3
7
A
A
AUX1 (e.g. PE)
4
8
12-114

80 mV, resolution 15 bits + sign
Terminal Assignment
TM-E15S24-A1 and 2AI TC Standard
CH1
M
1+
M
1–
M
ana
AUX1 (e.g. PE)
AUX1 must be ap-
plied to PE.
pp
Remarks
Channel 0: Terminals 1 to A4
Channel 1: Terminals 5 to A8
M+: Measuring line (positive)
M–: Measuring line (negative)
M
: Ground of the module
ana
Distributed I/O System ET 200S