Analog Electronic Modules
Measuring Ranges for Resistance Thermometer Ni x00 Standard
Table 12-10 SIMATIC S7 Format: Measuring Ranges Ni 100, 120, 200, 500, 1000 Standard in °C and °F
Ni x00
Units
Standard
in 5C
5
Dec.
Hex.
(1 digit =
0.15C)
> 295.0
32767
7FFF
295.0
2950
B86
H
:
:
:
250.1
2501
9C5
H
250.0
2500
9C4
H
:
:
:
–60.0
–600
FDA8
–60.1
–601
FDA7
:
:
:
–105.0
–1050
FBE6
< –105.0
–32768
8000
H
Measuring Ranges for Resistance Thermometer Ni x00 Climatic
Table 12-11 SIMATIC S7 Format: Measuring Ranges Ni 100, 120, 200, 500, 1000 Climatic in °C and °F
Ni x00
Units
Climatic
in 5C
5
Dec.
Hex.
(1 digit =
0.015C)
> 295.00
32767
7FFF
295.00
29500
733C
:
:
:
250.01
25001
61A9
250.00
25000
61A8
:
:
:
–60.00
–6000
E890
–60.01
–6001
E88F
:
:
:
–105.00
–10500
D6FC
< – 105.00
–32768
8000
H
12-12
Ni x00
Units
Standard
in 5C
5
Dec.
(1 digit =
0.15F)
> 563.0
32767
7FFF
H
563.0
5630
15FE
:
:
:
482.1
4821
12D5
482.0
4820
12D4
:
:
:
–76.0
–760
FD08
H
–76.1
–761
FD07
H
:
:
:
–157.0
–1570
F9DE
H
< –157.0
–32768
8000
Ni x00
Units
Climatic
in 5F
5
Dec.
(1 digit =
0.01 5F)
> 325.11
32767
7FFF
H
327.66
32766
7FFE
H
:
:
:
280.01
28001
6D61
H
280.00
28000
6D60
H
:
:
:
–76.00
–7600
E250
H
–76.01
–7601
E24F
H
:
:
:
–157.00
–15700
C2AC
H
< – 157.00
–32768
8000
Range
Hex.
Overflow
H
H
Overrange
H
H
Rated range
H
H
Underrange
H
Underflow
H
Range
Hex.
Overflow
H
H
Overrange
H
H
Rated range
H
H
Underrange
H
Underflow
H