Siemens ET 200S Manual page 350

Distributed i/o system
Hide thumbs Also See for ET 200S:
Table of Contents

Advertisement

Digital Electronic Modules
Table 11-19 Switching Capacity and Lifetime of the Relay Contacts
Resistive Load
For inductive load in
accordance with
IEC 947-5-1 DC 13/
IEC 947-5-1 DC 13/
AC 15
11.18
2RO NO/NC 24–48 VDC/5 A,
24–230 VAC/5 A Digital Electronic Module
(6ES7 132-4HB10-0AB0)
Note
If you connect an extra-low voltage system (SELV/ PELV) on one channel of the
relay module, you can only use an extra-low voltage system (SELV/ PELV) on the
other channel.
Features
S Digital electronic module with two relay outputs
S Output current 5 A per output
S Substitute value
S Parameter assignment length: 3 bytes
S Suitable for solenoid valves, DC contactors, and indicator lights
S Isolated from the supply voltage
S Normally open contact and normally closed contact
Caution
!
The rated supply voltage of the 2RO NO/NC 24–48 VDC/5 A, 24–230 VAC/5 A is
24 VDC. The 2RO NO/NC 24–48 VDC/5 A, 24–230 VAC/5 A can only be located
in a potential group with 24 VDC (from the power module).
11-74
Voltage
230 VAC
2.0 A
1.0 A
0.5 A
Current
Operating Cycles
(Typical)
0.1 million
0.3 million
1 million
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07