Wiring and assembly
5.4 Wiring the ET 200S
5.4.4

Wiring terminal modules with Fast Connect

Introduction
• In the case of terminal modules with Fast Connect, the individual wires are attached
• Fast Connect is a connection method that requires no conductor preparation (i. e., the
• Each terminal of the terminal module with Fast Connect has a test opening (e. g.
• End sleeves are not permitted.
• Diagram of the Fast Connect terminal module
(1)
(2)
(3)
(4)
Requirements
• Follow the wiring rules.
Required tools
3-mm screwdriver
Connectable wires
You can connect solid and flexible wires with PVC insulation with a wire cross-section of
0.5 mm
the same, they can be connected fifty times. You can find a list of the tested conductors at:
http://www.idc2.de
UL-compliant cables and connections
Wiring range for insulating piercing connection 22 -16 AWG solid/stranded PVC insulated
conductors, UL style no. 1015 only.
5-10
using a quick connection method that requires no stripping.
conductor insulation does not have to be stripped).
measuring the voltage). The test opening is suitable for probes with a maximum diameter
of O̸ 1.5 mm.
1
2
3
4
Opening for measuring, checking: max. O̸ 1.5 mm
Opening for 1 conductor: 0.5 ...1.5 mm
Locking mechanism open (the wire can be inserted)
Locking mechanism closed (the wire is connected)
up to 1.5 mm
(max. external diameter 3.2 mm). If the conductor cross-section is
2
2
2
Operating Instructions, 12/2005, A5E00515771-03
ET 200S