Analog Electronic Modules
12.1.2
Analog Value Representation for the Measuring Ranges of the
Analog Input Modules in SIMATIC S7 Format
Introduction
The tables in this section contain the digitized analog values for the measuring
ranges of the analog input modules.
The binary representation of the analog values is always the same, so these tables
only compare the measuring ranges and the units.
Measuring Ranges for Voltage:
Table 12-4 SIMATIC S7 Format: Measuring Ranges "80 mV, "2.5 V, "5 V and "10 V
Measuring
Measuring
Range
Range
" 80 mV
" 2.5 V
> 94.071
> 2.9397
94.071
2.9397
:
:
80.003
2.5001
80.000
2.5
60.000
1.86
:
:
– 60.000
– 1.86
– 80.000
– 2.50
– 80.003
– 2.5001
:
:
– 94.074
– 2.9397
< – 94.074
< – 2.9397
12-8
" 80 mV, " 2.5 V, " 5 V, " 10 V
Measuring
Measuring
Range
Range
" 5 V
" 10 V
> 5.8794
> 11.7589
5.8794
11.7589
:
:
5.0002
10.0004
5.00
10.00
3.75
7.50
:
:
– 3.75
– 7.50
– 5.00
– 10.00
– 5.0002
– 10.0004
:
:
– 5.8796
– 11.759
< – 5.8796
< – 11.759
Units
Decimal
Hexadec.
32767
7FFF
H
32511
7EFF
H
:
:
27649
6C01
H
27648
6C00
H
20736
5100
H
:
:
–20736
AF00
H
–27648
9400
H
–27649
93FF
H
:
:
–32512
8100
H
–32768
8000
H
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Range
Overflow
Overrange
Rated range
Underrange
Underflow