Configuration Options
Table 3-2
Interface Modules and the Applications for Which They Are Suited
S
Connecting the PROFIBUS-DP by means of
fiber-optic cable
S
Operation as a DPV0 slave
S
Direct communication
S
Width of the ET 200S: max. 1 m
S
Number of modules: max. 63
S
Connecting the PROFIBUS-DP by means of the
RS 485 interface
S
Use of fail-safe modules
S
Clocking as of 1.5 Mbps
S
Direct communication
S
Updating firmware via PROFIBUS-DP with
HWCONFIG
S
Operation as a DPV0 slave
– Acyclic data exchange (read/write data record):
class 2 services (e.g. updating firmware)
S
Operation as a DPV1 slave
– Acyclic data exchange (read/write data record):
class 2 services (e.g. updating firmware) and
class 1 services
– Diagnostic interrupts
– Hardware interrupts
– Insert/Remove-module interrupts
S
Width of the ET 200S: max. 1 m
S
Number of modules: max. 63
Rules for Setting Up a Fiber-Optic Cable Network with the IM 151-1 FO
STANDARD
For a fiber-optic cable network with nodes that have integrated fiber-optic cable
interfaces, note the following:
S The fiber-optic cable network can be set up only as a line segment.
S If you remove the fiber-optic cable from an integrated fiber-optic cable interface,
or the supply voltage to the IM151-1 FO STANDARD fails, all the downstream
nodes are no longer accessible.
3-6
Applications
Transmission rates:
9.6, 19.2, 45.45, 93.75,
187.5, 500 kbps
1.5, 12 Mbps
Transmission rates:
9.6, 19.2, 45.45, 93.75,
187.5, 500 kbps
1.5, 3, 6, 12 Mbps
Interface Module
IM 151-1 FO
STANDARD
IM151-1 HIGH
FEATURE
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07