Terminal Modules
Terminal Assignment
The following table shows the terminal assignment of the terminal module:
Table 9-6
Terminal Assignment of the TM-P30S44-A0 and TM-P30C44-A0 Terminal
Module
View
A
A
4
8
1
2
6
0
3
7
A
A
A
1
8
4
2
2
Caution
!
If high currents occur at DO 2 P and DO 2 M, you must wire terminals 11 and 15
(DO 2 P) and 12 and 16 (DO 2 M) in parallel.
Otherwise, the temperature of the terminals cannot be prevented from rising due
to the current load.
9-12
Terminal
3
24 VDC
A
M
4
5
AUX 1
1
9
3
1
6
24 VDC
4
1
1
1
5
1
7
M
6
6
A
AUX 1
8
9
DO 0 P
10
DO 0 M
11
DO 2 P
12
DO 2 M
13
DO 1 P
14
DO 1 M
15
DO 2 P
16
DO 2M
Designation
Load voltage of 24 VDC for: inserted
power module and associated potential
group. DO 0 and DO 1 and P1 and P2
voltage buses
Ground
Any connection for PE or voltage bus up
to the maximum rated load voltage of the
module
Load voltage of 24 VDC for: inserted
power module and associated potential
group. DO 0 and DO 1 and P1 and P2
voltage buses
Ground
Any connection for PE or voltage bus up
to the maximum rated load voltage of the
module
Connections for fail-safe digital output 0
(switching to P/M potential)
Connections (relay contacts) for fail-safe
switching of the voltage buses P1 and P2.
P1 and P2 can also be used as DO 2 M
P1 and P2 can also be used as DO 2 M
and DO 2 P (for a diagram of the wiring,
see the ET 200S Fail-Safe Modules
manual).
Connections for fail-safe digital output 0
(switching to P/M potential)
Connections (relay contacts) for fail-safe
switching of the voltage buses P1 and P2.
P1 and P2 can also be used as DO 2 M
P1 and P2 can also be used as DO 2 M
and DO 2 P (for a diagram of the wiring,
see the ET 200S Fail-Safe Modules
manual).
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07