13.2
Control and Feedback Interface (PIQ/PII)
You can configure the address space of the control and feedback interfaces of the
4 IQ-SENSE. You can choose between Standard and Enhanced.
Standard Features
S The 4 IQ-SENSE occupies 4 bits in the feedback interface.
S The 4 IQ-SENSE can be grouped in a single byte. Two 4 IQ-SENSE modules
can be grouped in each byte. See also Section 6.1.
S You can evaluate the circuit state of each channel using the feedback interface.
Enhanced Features
S The 4 IQ-SENSE occupies one byte in the control interface and one in the
feedback interface.
S You can use the control interface to specify the sensitivity and distance values
for each channel (IntelliTeach via "IQ-SENSE Opto" FB) and execute teach-in.
S You can use the feedback interface to evaluate the acquired sensitivity and
distance values (switching threshold) and the circuit state for each channel.
Prerequisites:
S You can use the "IQ-SENSE Opto" function block. The FB facilitates easy
access to the control and feedback interface.
S Please note that in this case PII equals PIQ.
S You can download the function block and the relevant product information on
the Internet at http://www.ad.siemens.de/csi_e/gsd.
Configuring the Address Space
Address
Space
Standard
Enhanced
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
With STEP7 as of V5.1,
ServicePack 3
In the hardware catalog of
HWCONFIG, choose
4IQ-SENSE Opto S.
In the hardware catalog of
HWCONFIG, choose
4IQ-SENSE Opto E.
4 IQ-SENSE
With STEP7 as of V4.02 or COM
PROFIBUS or other
configuration software
From the DDB file, choose
S 6ES7 138-4GA00-0AB0
IQ-SENSE Opto.
From the DDB file, choose
E 6ES7 138-4GA00-0AB0
IQ-SENSE Opto.