Analog Output Module Error Types
Table 6-15 Analog Output Module Error Types
Analog output
modules
2AO U
2AO I
16
Standard
Standard
2AO U
2AO I
High
High
Feature
Feature
9
D
–––
1
D
–––
2AO I
6
D
Standard
2AO I
High
Feature
1SSI
Table 6-16 1SSI
Error Type
1
00001: Short circuit
D
9
01001: Error
D
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Error Type
10000:
Module cannot use the
D
Parameter
parameter for the channel:
assignment
Inserted module does not
error
match the one configured.
Parameter assignment error.
01001: Error
Internal module error has
occurred (diagnostic
message on channel 0
applies to the whole
module).
00001: Short
Short circuit of the actuator
circuit
supply.
00110: Open
Line to the actuator
circuit
interrupted.
Meaning
Short circuit of the supply to the
absolute position encoder.
Internal module error occurred.
Load voltage from the power
module is too low.
Commissioning and Diagnostics
Meaning
Correct the configuration
(compare actual and desired
configuration).
Correct the parameter
assignment (parameter
assignment of wire break
diagnosis only with the permitted
measuring ranges).
Replace the module.
Correct the process wiring.
Correct the process wiring.
What to Do
Correct the process wiring.
Replace the module.
Correct the process wiring.
Check the load voltage.
What to Do