General Technical Specifications
7.4
Information on Insulation Testing, Safety Class, Degree of
Protection, and Rated Voltage of the ET 200S
Test Voltage
Insulation strength is demonstrated in the type test with the following test voltage in
accordance with IEC 61131-2:
Circuits with a Rated Voltage of U
Other Circuits or Ground
Pollution Severity/Overvoltage Category in Accordance with IEC 61131
S Pollution severity 2
S Overvoltage category
– When U
– When U
Safety Class
Safety class I to IEC 60536
IP 20 Degree of Protection
IP 20 protection in accordance with IEC 60529 for all ET 200S modules, which
means:
S Protection against contact with standard test probes
S Protection against foreign bodies with a diameter greater than 12.5 mm
S No special protection against water
7-10
to
e
< 50 V
< 150 V
< 250 V
= 120/ 230 VAC: III
N
= 24 VDC: II
N
Test Voltage
500 VDC
2500 VDC
4000 VDC
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07